How long will the NovaSeq 6000 UPS support the instrument should backup power not engage?

In the event a NovaSeq 6000 instrument loses power, the NovaSeq 6000 Site Prep Guide, page 11, indicates the Uninterruptable Power Supply (UPS) can, on average, support the instrument for:

  • 51 minutes at an average power consumption of 1.8kW (idle instrument).

  • 34 minutes at a peak power consumption of 2.8kW (running instrument).

For any feedback or questions regarding this article (Illumina Knowledge Article #6305), contact Illumina Technical Support techsupport@illumina.com.

Last updated

© 2023 Illumina, Inc. All rights reserved. All trademarks are the property of Illumina, Inc. or their respective owners. Trademark information: illumina.com/company/legal.html. Privacy policy: illumina.com/company/legal/privacy.html